We use cookies to provide you the best experience on our website. You can disable the cookies in your browser setting. If you continue to use the site without changing your settings, we will assume that you are happy to accept all the cookies used on this site.

Please refer to our Terms of Use for further details on cookies. Terms of Use

Through the following links, you can skip to the menu or to the main text in this page.

Kubota For Earth, For Life

Kubota Generator

Menu

Kubota GeneratorsJ112


*Image shown may not reflect actual package.

Prime Output 12.0 kVA (12.0 kW)
Standby Output 13.2 kVA (13.2 kW)
Specifications
MODEL Unit J112
Type - Revolving field, AC generator
Frequency Hz 50
Standby Output kVA (kW) 13.2 (13.2)
Prime Output kVA (kW) 12.0 (12.0)
Voltage - Single Phase V 220
Phase / Wire - 1/2
Power Factor - 1.0
No. of Poles - 2
Insulation Class Rotor coil; class F, Stator coil; class B
Type of Coupling - Direct coupled
AMPS
Single Phase 110V A N/A
Single Phase 127V A N/A
Single Phase 220V A 54.5
Single Phase 240V A N/A
Three Phase 220V A N/A
Three Phase 380V A N/A
Three Phase 415V A N/A
TERMINAL
Terminal - Available
DIESEL ENGINE
Type - Vertical, water-cooled, 4-cycle diesel engine
Model - D1005
No. of Cylinders - 3
Bore x Stroke mm 76.0 x 73.6
Displacement L 1.001
Engine Speed rpm 3000
Continuous Rated Output kW (HP) 14.4 (19.3)
Lubricant
(API classification)
- above CD grade
Oil Capacity L 4.3
Coolant Capacity L 3.3
Starting System - Electric - 12 volt DC
SET
Fuel - Diesel fuel No.2
(ASTM D975)
 Fuel
Consumption
at Full Load L/h (gal./h) 4.6 (1.2)
at 3/4 Load L/h (gal./h) 3.7 (1.0)
at 1/2 Load L/h (gal./h) 3.0 (0.8)
at 1/4 Load L/h (gal./h) 2.4 (0.6)
Fuel Tank Capacity L (gal.) 79.0 (20.9)
 Continuous
Operation
Hours
at Full Load h 17.0
at 3/4 Load h 21.2
at 1/2 Load h 26.1
at 1/4 Load h 33.5
Battery (Ah/5 h) - 12 V (55 Ah)
Dimensions
L x W x H
mm 1215 x 611 x 922
Approx. Net Weight kg 340
Sound Level
(Full Load at 23 ft. [7m])
dB (A) 76.5
Emergency Stop System - In case of abnormal: Oil pressure, water temperature, fan belt broken